Consider a large classroom on a hot summer day with 150 students, each dissipating 60 W of

Question:

Consider a large classroom on a hot summer day with 150 students, each dissipating 60 W of sensible heat. All the lights, with 6.0 kW of rated power, are kept on. The room has no external walls, and thus heat gain through the walls and the roof is negligible. Chilled air is available at 15°C, and the temperature of the return air is not to exceed 25°C. Determine the required flow rate of air, in kg/s, that needs to be supplied to the room to keep the average temperature of the room constant. Answer: 1.49 kg/s
Fantastic news! We've Found the answer you've been seeking!

Step by Step Answer:

Related Book For  book-img-for-question

Heat Transfer

ISBN: 978-0073529363

10th edition

Authors: Jack Holman

Question Posted: