A counter-flow heat exchanger is used to cool oil (c p = 2.20 kJ/kg K) from
Question:
A counter-flow heat exchanger is used to cool oil (cp = 2.20 kJ/kg · K) from 110°C to 85°C at a rate of 0.75 kg/s by cold water (cp = 4.18 kJ/kg · K) that enters the heat exchanger at 20°C at a rate of 0.6 kg/s. If the overall heat transfer coefficient is 800 W/m2 · K, the heat transfer area of the heat exchanger is
(a) 0.745 m2
(b) 0.760 m2
(c) 0.775 m2
(d) 0.790 m2
(e) 0.805 m2