For a three-phase fault at the spark location shown in the figure below with all equipment three-phase

Question:

For a three-phase fault at the spark location shown in the figure below with all equipment three-phase and generator of finite size, determine the symmetrical  rms fault current. Ignore the series resistance (but not the reactance) of the transformer and the generator. Assume all cables short with negligible R and X, and follow the following steps:

(1) As is commonly done by power engineers, convert the system to % values based on the kilovolt-ampere and voltage ratings of the transformer feeding the fault. Then, determine the fault current in amperes at the fault location and also at the generator terminals using the voltage ratio.

(2) Repeat the calculation by converting the system to % Z values based on the kilovolt-ampere and voltage ratings of the generator, and then determine the fault current in amperes at the generator and the transformer terminals and compare it with (1).

2 E/Xa 2 Ej/Xa 2 Eg/Xa + Ifault E Prefault field excitation voltage of generator = Subtransient I" Envelope


Gen 100 MVA, 3-ph 11 kV, X =18% (Not infinite bus) 25 MVA, 3-ph, 11/4.2 kV, Z = 7% -000 ele 50 MVA, 11 kV

Fantastic news! We've Found the answer you've been seeking!

Step by Step Answer:

Question Posted: