Repeat Problem 16-17 if the load power factor is a leading 0.92 . Data From Problem 16-17

Question:

Repeat Problem 16-17 if the load power factor is a leading 0.92 .


Data From Problem 16-17

The average power delivered to the load \(Z_{\mathrm{L}}\) in Figure P16-17 is \(46 \mathrm{~kW}\) at a lagging power factor of 0.7. The load voltage is \(2.4 \mathrm{kV}(\mathrm{rms})\) and the line has an impedance of \(Z_{\mathrm{W}}=1\) \(+j \Omega /\) wire. Find the apparent power produced by the source and the magnitude of the source voltage.