A 15-MVA, three-phase, 6.6-kV generator with subtransient reactance X d = 15% feeds a three-phase, 1-MVA, 6.6-kV/480
Question:
A 15-MVA, three-phase, 6.6-kV generator with subtransient reactance X′′d = 15% feeds a three-phase, 1-MVA, 6.6-kV/480 V transformer with Xtrfr = 7% via cable that has a leakage reactance Xcable = 2.2 mΩ/phase as shown in the figure below. Neglecting all resistances, determine the symmetrical rms value and the worst-case first offset peak of the fault current for a three - phase fault at the transformer output terminals using:
(1) Reactance values in percent and
(2) All reactance values in ohms.