Question: A Step-Up Transformer A transformer connected to a 120-V (rms) ac line is to supply 13,000 V (rms) for a neon sign. To reduce shock
A Step-Up Transformer A transformer connected to a 120-V (rms) ac line is to supply 13,000 V (rms) for a neon sign. To reduce shock hazard, a fuse is to be inserted in the primary circuit; the fuse is to blow when the rms current in the secondary circuit exceeds 8.50rnA.
(a) What is the ratio of secondary to primary toms of the transformer?
(b) What power must be supplied to the transformer when the rms secondary current is 8.50rnA?
(c) What current rating should the fuse in the primary circuit have?
Step by Step Solution
3.38 Rating (182 Votes )
There are 3 Steps involved in it
IDENTIFY P VI and P P2 SET UP V120 V V 13000 V N V 13000 V N V 120 ... View full answer