Question: Refrigerant-12 at 95C, x 0.1 flowing at 2 kg/s is brought to saturated vapor in a constant-pressure heat exchanger. The energy is supplied by a
Refrigerant-12 at 95C, x 0.1 flowing at 2 kg/s is brought to saturated vapor in a constant-pressure heat exchanger. The energy is supplied by a heat pump with a low temperature of 10C. Find the required power input to the heat pump.