Question: Consider proportional only control of the level control system in Fig. 11.16. The level transmitter has a span of 10 ft. and a zero of
(a) What is the offset?
(b) What are the gains Kmand Kpin Fig. 11.16? (Give their units also)
(c) How could the controller be modified to obtain zero offset?
![Qi [m³/min] Н' Hap P' Нур [m] K, ts + 1 Кт G(s) Кір K, [%] [%] [%] [psi) [m3/min] [m] Н' Hт [%] [m] Figure 1](https://dsd5zvtm8ll6.cloudfront.net/si.question.images/images/question_images/1533/2/9/3/5705b643402b4e531533275809645.jpg)
Qi [m/min] ' Hap P' [m] K, ts + 1 G(s) K, [%] [%] [%] [psi) [m3/min] [m] ' H [%] [m] Figure 11.16 Block diagram for level control system.
Step by Step Solution
3.41 Rating (164 Votes )
There are 3 Steps involved in it
a Offset h ss h final 2200 2192 008 ft b We have ... View full answer