Question: Consider proportional only control of the level control system in Fig. 11.16. The level transmitter has a span of 10 ft. and a zero of

Consider proportional only control of the level control system in Fig. 11.16. The level transmitter has a span of 10 ft. and a zero of 15 ft. Recall that the standard instrument ranges are 4 to 20 mA and 3 to 15 psia. The nominal design conditions are h = 20 ft. The controller has a gain of 5 while the gain for the control valve is K= 0.4 cfm/psi, respectively. The time constant for the tank is Ï„ = 5 min. After the set-point is changed from 20 to 22 ft, the tank level eventually reaches a new steady-state value of 21.92 ft.
(a) What is the offset?
(b) What are the gains Kmand Kpin Fig. 11.16? (Give their units also)
(c) How could the controller be modified to obtain zero offset?

Qi [m³/min] Н' Hap P' Нур [m] K, ts + 1 Кт G(s) Кір K, [%] [%] [%] [psi) [m3/min] [m] Н' Hт [%] [m] Figure 1

Qi [m/min] ' Hap P' [m] K, ts + 1 G(s) K, [%] [%] [%] [psi) [m3/min] [m] ' H [%] [m] Figure 11.16 Block diagram for level control system.