Repeat Problem 7.24, except place the fault midway between buses 2 and 4. Determining the values for line faults requires that the line be split, with a fictitious bus added at the point of the fault. The original line's impedance is then allocated to the two new lines based on the fault location, \(50 \%\) each for this problem. Fault calculations are then the same as for a bus fault. This is done automatically in PowerWorld Simulator by first right-clicking on a line, and then selecting "Fault." The Fault dialog appears as before, except now the fault type is changed to "In-Line Fault." Set the location percentage field to \(50 \%\) to model a fault midway between buses 2 and 4 .
Data From Problem 7.24:-
PowerWorld Simulator case Problem 7.24 models the system shown in Figure 7.14 with all data on a 1000-MVA base. Using PowerWorld Simulator, determine the current supplied by each generator and the per-unit bus voltage magnitudes at each bus for a fault at bus 2 .

FIGURE 7.14 G1 T1 T3 150 150 Problems 7.12, 7.13, 7.19, 7.24, 7.25, 7.26 YA YA j50 n t G2 122 3