Question: A single-phase step-down transformer is rated (13 mathrm{MVA}, 66 mathrm{kV} / 11.5 mathrm{kV}). With the (11.5 mathrm{kV}) winding short-circuited, rated current flows when the voltage

A single-phase step-down transformer is rated \(13 \mathrm{MVA}, 66 \mathrm{kV} / 11.5 \mathrm{kV}\). With the \(11.5 \mathrm{kV}\) winding short-circuited, rated current flows when the voltage applied to the primary is \(5.5 \mathrm{kV}\). The power input is read as \(100 \mathrm{~kW}\). Determine \(\mathrm{R}_{\mathrm{eq} 1}\) and \(\mathrm{X}_{\mathrm{eq} 1}\) in ohms referred to the high-voltage winding.

Step by Step Solution

There are 3 Steps involved in it

1 Expert Approved Answer
Step: 1 Unlock

Determining Equivalent Resistance and Reactance of the Transformer 1 Given Information Transformer rating 13 MVA 66 kV 115 kV Shortcircuit test Primar... View full answer