An industrial load consisting of a bank of induction motors consumes (50 mathrm{~kW}) at a power factor

Question:

An industrial load consisting of a bank of induction motors consumes \(50 \mathrm{~kW}\) at a power factor of 0.8 lagging from a \(220-\mathrm{V}, 60-\mathrm{Hz}\), single-phase source. By placing a bank of capacitors in parallel with the load, the resultant power factor is to be raised to \(0.95 \mathrm{lag}\) ging. Find the net capacitance of the capacitor bank in \(\mu \mathrm{F}\) that is required.

Fantastic news! We've Found the answer you've been seeking!

Step by Step Answer:

Related Book For  answer-question

Power System Analysis And Design

ISBN: 9781305632134

6th Edition

Authors: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma

Question Posted: