Repeat Problem 9.28 for the two-conductors-open fault shown in Figure 9.21 (b). The fault conditions in the
Question:
Repeat Problem 9.28 for the two-conductors-open fault shown in Figure 9.21 (b). The fault conditions in the phase domain are \[ I_{b}=I_{b^{\prime}}=I_{c}=I_{c^{\prime}}=0 \text { and } V_{a a^{\prime}}=0 \]
Problem 9.28
As shown in Figure 9.21(a), two three-phase buses \(a b c\) and \(a^{\prime} b^{\prime} c^{\prime}\) are interconnected by short circuits between phases \(b\) and \(b^{\prime}\) and between \(c\) and \(c^{\prime}\), with an open circuit between phases \(a\) and \(a^{\prime}\). The fault conditions in the phase domain are \(I_{a}=I_{a^{\prime}}=0\) and \(V_{b b^{\prime}}=V_{c c^{\prime}}=0\). Determine the fault conditions in the sequence domain and verify the interconnection of the sequence networks as shown in Figure 9.15 for this oneconductor-open fault.
Figure 9.21
Figure 9.15
Step by Step Answer:
Power System Analysis And Design
ISBN: 9781305632134
6th Edition
Authors: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma