Question: Two smart transmitters have been selected for a SIF design. The logic solver is programmed to trip if either transmitter indicates a dangerous condition (1oo2).
Two smart transmitters have been selected for a SIF design. The logic solver is programmed to trip if either transmitter indicates a dangerous condition (1oo2). The manufacturer’s data sheet lists the SFF as 92.4
%. Based on architecture constraints, to what SIL level is this design qualified per IEC 61508, Route 1H? IEC 61508:2010, Route 2H?
Step by Step Solution
3.41 Rating (160 Votes )
There are 3 Steps involved in it
Answer The smart transmitters are type B equipment A ... View full answer