Question: A transmission line that has a resistance per unit length of 4.50 x 10-4 (/m is to be used to transmit 5.00 MW over 400
(a) What is the line loss if a transformer is used to step up the voltage to 500 kV?
(b) What fraction of the input power is lost to the line under these circumstances?
(c) What If? What difficulties would be encountered in attempting to transmit the 5.00 MW at the generator voltage of 4.50 kV?
Step by Step Solution
3.41 Rating (148 Votes )
There are 3 Steps involved in it
a b c R45010 2M 644105 m 290 2 and Imms Ross 1ms R 100 A 2902 290 kW ... View full answer
Get step-by-step solutions from verified subject matter experts