Question: A R-12 heat pump cycle shown in Fig. P6.71 has a R-12 flow rate of 0.05 kg/s with 4 kW into the compressor. The following
A R-12 heat pump cycle shown in Fig. P6.71 has a R-12 flow rate of 0.05 kg/s with 4 kW into the compressor. The following data are given
.png)
Calculate the heat transfer from the compressor, the heat transfer from the R-12 in the condenser and the heat transfer to the R-12 in the evaporator.
State PkPa 250 1230 1200 320300 290 ToC h kJ/kg 260 253 79.7 4 120 110 45 188 191