Question: Hot-air heating control systems for large buildings may involve significant dead time if there is a large distance between the furnace and the room being
.png)
Heated (Figure P12.19). Proportional control applied to the specific plant
Gp(s) = 1 / 0.1s + 1
Has the gain KP = 10. The time units are minutes. How large can the dead time D between the controller and the plant be if the phase margin must be no less than 40o?
Temperature sensor. Room Blower Heat exchanger Steam