Question: In an actual refrigeration cycle using R-12 as the working fluid, the refrigerant flow rate is 0.05 kg/s. Vapor enters the compressor at 150 kPa,

In an actual refrigeration cycle using R-12 as the working fluid, the refrigerant flow rate is 0.05 kg/s. Vapor enters the compressor at 150 kPa, −10°C, and leaves at 1.2 MPa, 75°C. The power input to the compressor is measured and found be 2.4 kW. The refrigerant enters the expansion valve at 1.15 MPa, 40°C, and leaves the evaporator at 175 kPa, −15°C. Determine the entropy generation in the compression process, the refrigeration capacity and the coefficient of performance for this cycle.

Step by Step Solution

3.39 Rating (168 Votes )

There are 3 Steps involved in it

1 Expert Approved Answer
Step: 1 Unlock

Actual refrigeration cycle 1 compressor inlet T 1 10 o C ... View full answer

blur-text-image
Question Has Been Solved by an Expert!

Get step-by-step solutions from verified subject matter experts

Step: 2 Unlock
Step: 3 Unlock

Document Format (1 attachment)

Word file Icon

774-P-T-F-L (1312).docx

120 KBs Word File

Students Have Also Explored These Related Thermodynamics Questions!