Question: A balanced -connected load-1 has Z LL1 = 6 + j9 in each phase of . It is connected in parallel with a balanced
A balanced Δ-connected load-1 has ZLL1 = 6 + j9 Ω in each phase of Δ. It is connected in parallel with a balanced Y-connected load-2 with ZLN2 = 2 + j3 Ω in each phase of Y. If these two parallel loads are powered by a three-phase, Y-connected generator with a 480-V line voltage, determine the line current at the generator terminals and the real power delivered by the generator.