Question: A single-phase 120 kVA, 2400/240 V, 60-Hz distribution transformer is used as a step-down trans- former. The load, which is connected to the 240-V
A single-phase 120 kVA, 2400/240 V, 60-Hz distribution transformer is used as a step-down trans- former. The load, which is connected to the 240-V secondary winding, absorbs 110 kVA at 0.85 power factor lagging and is at 230 V. Winding resistances are R-2 52 and R -0.05 52; leakage reactances are X = 2.5 2 and X-0.02 2. Calculate the following (using actual values): a) equivalent series impedance, referred to the primary b) primary voltage c) the real and reactive power supplied to the primary winding Using transformer ratings as base values, rework Problem in per-unit.
Step by Step Solution
3.37 Rating (156 Votes )
There are 3 Steps involved in it
Answer Given data Transformer rating 120 kVA Primary voltage VP 2400 V Secondary voltage VS 240 V Load power Sload 110 kVA Power factor cos 085 laggin... View full answer