A three-phase, (500-mathrm{MVA}, 345 mathrm{kV} Delta / 500 mathrm{kV}) Y transformer is protected by differential relays with
Question:
A three-phase, \(500-\mathrm{MVA}, 345 \mathrm{kV} \Delta / 500 \mathrm{kV}\) Y transformer is protected by differential relays with taps. Select CT ratios, CT connections, and relay tap settings. Determine the currents in the transformer and in the CTs at rated conditions. Also determine the percentage mismatch for the selected relay tap settings. Available relay tap settings are given in Problem 10.26.
Problem 10.26
A single-phase, 5-MVA, 20/8.66-kV transformer is protected by a differential relay with taps. Available relay tap settings are 5:5, 5:5.5, 5:6.6, 5:7.3, 5:8, 5:9, and 5:10, giving tap ratios of 1.00, 1.10, 1.32, 1.46, 1.60, 1.80, and 2.00. Select CT ratios and relay tap settings. Also, determine the percentage mismatch for the selected tap setting.
Step by Step Answer:
Power System Analysis And Design
ISBN: 9781305632134
6th Edition