As shown in Figure 7.21, a 25-MVA, 13.8-kV, 60-Hz, synchronous generator with (mathrm{X}_{d}{ }^{prime prime}=0.15) per unit

Question:

As shown in Figure 7.21, a 25-MVA, 13.8-kV, 60-Hz, synchronous generator with \(\mathrm{X}_{d}{ }^{\prime \prime}=0.15\) per unit is connected through a transformer to a bus that supplies four identical motors. The rating of the three-phase transformer is 25 MVA and \(13.8 / 6.9 \mathrm{kV}\) with a leakage reactance of 0.1 per unit. Each motor has a subtransient reactance \(\mathrm{X}_{d}{ }^{\prime \prime}=0.2\) per unit on a base of \(5 \mathrm{MVA}\) and \(6.9 \mathrm{kV}\). A three-phase fault occurs at point \(\mathrm{P}\), when the bus voltage at the motors is \(6.9 \mathrm{kV}\). Determine

(a) the subtransient fault current,

(b) the subtransient current through breaker A, and

(c) the symmetrical short-circuit interrupting current (as defined for circuit breaker applications) in the fault and in breaker A.

image text in transcribed

Fantastic news! We've Found the answer you've been seeking!

Step by Step Answer:

Related Book For  answer-question

Power System Analysis And Design

ISBN: 9781305632134

6th Edition

Authors: J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma

Question Posted: