Repeat Problem 9.24 for a single line-to-ground arcing fault with arc impedance (Z_{mathrm{F}}=0+j 0.1 ) per unit.

Question:

Repeat Problem 9.24 for a single line-to-ground arcing fault with arc impedance \(Z_{\mathrm{F}}=0+j 0.1 \) per unit.

Problem 9.24

Determine the subtransient fault current in per-unit and in \(\mathrm{kA}\), as well as contributions to the fault current from each line, transformer, and generator connected to the fault bus for a bolted single line-to-ground fault at the fault bus selected in Problem 9.9.

Problem 9.9

Faults at bus \(n\) in Problem 9.8 are of interest (the instructor selects \(n=\) 1, 2, 3, 4, or 5). Determine the Thévenin equivalent of each sequence network as viewed from the fault bus. Prefault voltage is 1.0 per unit. Prefault load currents and \(\Delta-Y\) phase shifts are neglected.