Question: Rework Example 14.3 with R Load = 40 / R Load = 40 / phase, X Load = 60 / X Load

Rework Example 14.3 with RLoad =40Ω/ phase, XLoad =60Ω/ phase, and XC=60Ω/ phase.

Example 14.3

Figure 14.21 shows a single-line diagram of a 13.8kV primary feeder supplying power to a load at the end of the feeder. A shunt capacitor bank is located at the load bus. Assume that the voltage at the sending end of the feeder is 5% above rated and that the load is Y-connected with RLoad =20Ω/ phase in parallel with load jXLoad =j40Ω /phase.

(a) With the shunt capacitor bank out of service, calculate the following: (1) line current; (2) voltage drop across the line; (3) load voltage; (4) real and reactive power delivered to the load; (5) load power factor; (6) real and reactive line losses; and (7) real power, reactive power, and apparent power delivered by the distribution substation.

(b) The capacitor bank is Y-connected with a reactance XC=40Ω/ phase. With the shunt capacitor bank in service, redo the calculations. Also calculate the reactive power supplied by the capacitor bank.

(c) Compare the results of (a) and (b).

Distribution substation transformer 138/13.8 kV Sending end voltage Vs Feeder impedance RLINE

Distribution substation transformer 138/13.8 kV Sending end voltage Vs Feeder impedance RLINE IXLINE m j6 (2 ww 39 3 -xc = T Shunt capacitor bank Load voltage VLOAD XLOAD www Load RLOAD

Step by Step Solution

3.34 Rating (151 Votes )

There are 3 Steps involved in it

1 Expert Approved Answer
Step: 1 Unlock blur-text-image
Question Has Been Solved by an Expert!

Get step-by-step solutions from verified subject matter experts

Step: 2 Unlock
Step: 3 Unlock

Students Have Also Explored These Related Systems Analysis Design Questions!