Question: Three loads are connected in parallel to a 1200 V rms source. Load 1 absorbs 60 kVAR at pf = 0.85 lagging, load 2 absorbs
(a) Find the equivalent impedance.
(b) Calculate the power factor of the parallel combination.
(c) Determine the current supplied by the source.
Step by Step Solution
3.40 Rating (169 Votes )
There are 3 Steps involved in it
a For load 1 Q 1 60 kVAR pf 085 or 1 3179 Q 1 S 1 sin 1 60k or S 1 11389k and P 1 ... View full answer
Get step-by-step solutions from verified subject matter experts