Question: Re-determine the Example 9_8 fault currents, except with a new line installed between buses 2 and 5. The parameters for this new line should be

Re-determine the Example 9_8 fault currents, except with a new line installed between buses 2 and 5. The parameters for this new line should be identical to those of the existing line between buses 2 and 5 . The new line is not mutually coupled to any other line. Are the fault currents larger or smaller than the Example 9_8 values?

Example 9_8

Consider the five-bus power system whose single-line diagram is shown in Figure 6.2. Machine, line, and transformer data are given in Tables 9.1, 9.2, and 9.3. Note that the neutrals of both transformers and generator 1 are solidly grounded, as indicated by a neutral reactance of zero for this equipment. However, a neutral reactance equal to 0.0025 per unit is connected to the generator 2 neutral. The prefault voltage is 1.05 per unit. Using PowerWorld Simulator, determine the fault currents and voltages for a bolted single line-to-ground fault at bus 1 , then bus 2 , and so on to bus 5 .

Figure 6.2

400 MVA 15 kV B1 1 400 MVA 15/345 kV 5 851

Tables (9.1, 9.2, 9.3)

0 B52 345 kV 100 mi B21 2- Line 2 Line 3

400 MVA 15 kV B1 1 400 MVA 15/345 kV 5 851 0 B52 345 kV 100 mi B21 2- Line 2 Line 3 345 kV 50 mi 280 Mvar Line 1 B41 B42 345 kV 200 mi B22 4 800 MW T2 800 MVA 345/15 kV B3 3 40 Mvar 80 MW 520 MW 800 MVA 15 kV

Step by Step Solution

3.34 Rating (151 Votes )

There are 3 Steps involved in it

1 Expert Approved Answer
Step: 1 Unlock blur-text-image
Question Has Been Solved by an Expert!

Get step-by-step solutions from verified subject matter experts

Step: 2 Unlock
Step: 3 Unlock

Students Have Also Explored These Related Systems Analysis Design Questions!