The 60-Hz line voltage for a 60-kW, 0.76-pf lagging industrial load is 240 < 0o V rms.

Question:

The 60-Hz line voltage for a 60-kW, 0.76-pf lagging industrial load is 240 < 0o V rms. Find the value of capacitance that when placed in parallel with the load will raise the power factor to 0.9 lagging.