Question: Redo Example 6.17 with the assumption that the per-unit reactance on the line between buses 2 and 5 is changed from 0.05 to 0.03. Example

Redo Example 6.17 with the assumption that the per-unit reactance on the line between buses 2 and 5 is changed from 0.05 to 0.03.

Example 6.17

Determine the dc power flow solution for the five bus system from Example 6.9.

Example 6.9

Figure 6.2 shows a single-line diagram of a five-bus power system. Input data are given in Tables 6.1, 6.2, and 6.3. As shown in Table 6.1, bus 1, to which a generator is connected, is the swing bus. Bus 3, to which a generator and a load are connected, is a voltage-controlled bus. Buses 2, 4, and 5 are load buses. Note that the loads at buses 2 and 3 are inductive since \(\mathrm{Q}_{2}=-\mathrm{Q}_{\mathrm{L} 2}=-2.8\) and \(-\mathrm{Q}_{\mathrm{L} 3}=\) -0.4 are negative.

For each bus \(k\), determine which of the variables \(\mathrm{V}_{k}, \delta_{k}, \mathrm{P}_{k}\), and \(\mathrm{Q}_{k}\) are input data and which are unknowns. Also, compute the elements of the second row of \(\boldsymbol{Y}_{\text {bus }}\).

Figure 6.2

400 MVA 15 kV B1 400 MVA 15/345 KV 5 B51 2

Table 6.1

B52 345 kV 100 mi B21 Line 3 345 kV 50 mi

Table 6.2

280 Mvar, B41 B42 345 kV 200 mi B22 800 MW T2

400 MVA 15 kV B1 400 MVA 15/345 KV 5 B51 2 B52 345 kV 100 mi B21 Line 3 345 kV 50 mi 280 Mvar, B41 B42 345 kV 200 mi B22 800 MW T2 800 MVA 345/15 kV B3 3 40 Mvar 80 MW 520 MW 800 MVA 15 kV

Step by Step Solution

3.32 Rating (146 Votes )

There are 3 Steps involved in it

1 Expert Approved Answer
Step: 1 Unlock blur-text-image
Question Has Been Solved by an Expert!

Get step-by-step solutions from verified subject matter experts

Step: 2 Unlock
Step: 3 Unlock

Students Have Also Explored These Related Systems Analysis Design Questions!